GlossaryRS-485
RS-485
RS-485, standardized as TIA-485-A, is an electrical standard for sending serial data as a differential signal over a twisted pair, so many devices can share one bus over long cables in electrically noisy places. It defines drivers, receivers and line voltages, not the data format, which usually comes from a UART and a protocol such as Modbus.
How it works
Each transceiver drives two lines, A and B, with opposite polarity. The receiver reads the voltage difference between them, so noise that couples equally onto both wires cancels out. Half-duplex RS-485 uses one pair, and devices take turns by enabling and disabling their drivers. Full-duplex links use two pairs.
The bus is a single trunk with short stubs to each device and a termination resistor at each end to absorb reflections. Bias resistors hold the idle line in a known state when no device is driving it. The standard rates bus loading in unit loads, and the Modbus serial line specification allows 32 devices on a segment without a repeater, with more possible when transceivers present fractional loads. That specification also ties maximum cable length to baud rate: longer runs need lower speeds.
RS-485 vs CAN bus
Both use a differential twisted pair. CAN adds arbitration, error detection and retransmission in hardware, so any node can transmit and collisions resolve without a master. RS-485 is only a physical layer. Firmware decides who talks, usually with one master polling the other devices. RS-485 is simple to add to any UART and can run at high baud rates, and CAN gives more robust multi-master messaging without extra protocol work.
Why it matters
Single-ended UART links fail over long cables and near motors. RS-485 carries the same serial data across a robot or machine reliably, with low-cost transceivers. Many smart servos, encoders, sensors and industrial devices offer RS-485 interfaces, so it is often the link a design has to support.
How to get it right
- Wire a daisy-chained trunk, not a star, and keep stubs short.
- Terminate both ends of the trunk, and only the ends.
- Add bias resistors at one point so idle lines read as a defined state.
- Control driver enable timing tightly so devices do not talk over each other.
- Use twisted pair cable, and carry a ground reference or isolate the transceivers.
- Add TVS protection where cables leave the enclosure.
RS-485 in robotics and drone hardware
Robot arms and mobile bases use RS-485 to reach smart servos, joint controllers and sensors through the harness, often at high baud rates. On drones it links some gimbals, payloads and industrial sensors. Board designers place the transceiver, termination and protection next to the connector, and decide whether termination is fitted or switchable for each board position on the bus.